Final | 2/11/2018 | 2/12/2018 | 2/12/2018 | A | PASS |
Tom Saunders
|
|
|
Key is under the recycle bin if you would like to go inside the house no one is living in the house. Phone #: ###-#### Inspection requested via web by Jay Symonds...ok to final
|
Electrical Rough-In | 11/20/2017 | 11/20/2017 | 11/20/2017 | A | CANC |
Tom Saunders
|
|
|
Key is under mat by the door next to panel for entry to house. House is empty. Phone #: ###-#### Inspection requested via web by Jay Symonds...needed perm service added
|
Rough-In Permanent Service | 11/20/2017 | 11/20/2017 | 11/20/2017 | A | PASS |
Tom Saunders
|
|
|
Key is under mat by the door next to panel for entry to house. House is empty. Phone #: ###-#### Inspection requested via web by Jay Symonds....corrections made...p/s o/h rec ok...will need panel labelled and schedule final
|
Permanent Service | 10/31/2017 | 10/31/2017 | 10/31/2017 | P | FAIL |
Tom Saunders
|
|
|
White door to the left of meter main is open if you need to go in and no one lives there house is empty. Phone #: ###-#### Inspection requested via web by Jay Symonds...
address life safety issues before power can be turned on 1) overhead power to shop needs proper clearance 16' or removed 2) overhead power to house over deck needs proper clearances - 12' 3) exterior light fixture needs reinstalled or wires safed off 4) panel needs labelling 5) pond by service- GFI protection of power serving pond or completely removal of power
|