DOC - Permit Finaled | | | 10/18/2018 | | DONE |
|
|
|
project finished out by other Electrical Contractor under ELE18-03898
|
Conference | 9/21/2018 | 9/21/2018 | 9/21/2018 | P | PASS |
Rock A. Hudson
|
|
|
Spoke with general foreman on site. All work performed after 9-14-18 must be done and permitted by a licenced contractor due to original contractor no longer in business.
|
Final | 9/13/2018 | 9/14/2018 | 9/14/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Requesting partial final for TCO. Contact is Kory Peterson Phone #: ###-#### Inspection requested via web by Clint Tate Contact informed me of Quality Electric are no longer open for business. A new contractor has taken over job. Areas are cluttered with equipment and areas are taped off so must reschedule when access available to all areas. Unable to locate general foreman or new electrical contractor.
|
Electrical Rough-In | 9/6/2018 | 9/7/2018 | 9/7/2018 | A | PASS |
Mark Moncarr
|
|
|
Requesting rough inspection on the back bar and above t-grid ceilings Phone #: ###-#### Inspection requested via web by Clint Tate Ok cover ceiling in kitch area. Back bar ok cover. 1 4sq needs mounted after beer taps installed. Box has grd pigtail.
|
Electrical Rough-In | 7/11/2018 | 7/12/2018 | 7/12/2018 | A | PASS |
Rock A. Hudson
|
|
|
Requesting re-inspection of the panel wall where the plumbing lines have been relocated per the field meeting Phone #: ###-#### Inspection requested via web by Clint Tate Panel wall rough in ok cover
|
Conference | 7/2/2018 | 7/3/2018 | 7/3/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Requesting an inspection consultation to review the panel wall that failed inspection previously. Specifically requesting Daryl to review any possible solutions to this issue. Phone #: ###-#### Inspection requested via web by Clint Tate As noted dedicated electrical space width and depth of panel board shall be clear for future expansion as per 110.26(E)(1)(a). As per conversation with Daryl DeGrange if only way to reconnect to pipes passing thru floor is in original area, only the amount permitted would be a 90 degree connector to leave dedicated electrical space.
|
Conference | 6/27/2018 | 6/28/2018 | 6/28/2018 | P | NH |
Rock A. Hudson
|
|
|
Requesting a consultation with Daryl specifically to review the panel wall which failed inspection on June 21st. The General Contractor will be scheduling the plumbing inspector as well to review all possible solutions. Please provide 1/2 hour notice before arriving to site to ensure all parties are present. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Called contact and explained Chief Electrical Inspector is off thru end of week and should return July 2. I told I had a meeting with Chief about correction and he agreed shall be code compliant. If would still like to meet will have to wait until Monday when he returns.
|
Electrical Rough-In | 6/20/2018 | 6/21/2018 | 6/21/2018 | A | PASS |
Rock A. Hudson
|
|
|
Requesting partial rough for bar area Phone #: ###-#### Inspection requested via web by Clint Tate Bar 1/2 wall only rough in ok cover
|
Electrical Rough-In | 6/21/2018 | 6/21/2018 | 6/21/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Requesting partial rough for bar area Phone #: ###-#### Inspection requested via web by Clint Tate Panel wall. 110.26(E)(1)1a- Space equal to width and depth of equipment shall be dedicated electrical space and shall have no other systems in this space. below panels
|
Electrical Rough-In | 6/4/2018 | 6/5/2018 | 6/5/2018 | A | PASS |
Rock A. Hudson
|
|
|
Contact name: Luke Hardy Phone #: ###-#### Inspection requested via web by Clint Tate Level 1 vestibules and level 2 chase to roof rough in ok cover
|
Electrical Rough-In | 5/10/2018 | 5/11/2018 | 5/11/2018 | P | PASS |
Rock A. Hudson
|
|
|
Requesting rough-in inspection for the new restaurant. Contact is Luke Hardy ###-####. Phone #: ###-#### Inspection requested via web by Clint Tate Wall rough in ok cover
|
Electrical Rough-In | 4/3/2018 | 4/3/2018 | 4/3/2018 | P | PASS |
Rock A. Hudson
|
|
|
Discussed show window receptacle requirements. Windows above garage style doors used as windows shall be concidered windows that could be used to advertise and shall have minimum required receptacles installed. NEC definitions. Show Window. Any window, including windows above doors, used or designed to be used for the display of goods or advertising material, whether it is fully or partly enclosed or entirely open at the rear and whether or not it has a platform raised higher than the street floor level. (CMP-2) Warm and dry storage rooms only walls and hardlids rough in ok cover.
|
Conference | 2/28/2018 | 2/28/2018 | 2/28/2018 | P | DONE |
Rock A. Hudson
|
|
|
Discussed stairway to alley lighting and sump room. On stairway to alley the lighting has been removed for stairway and shall be reinstalled asap as this path is being used daily. Sump pump room will be used as a spray down room. A pressure washer will be present in room. Room shall be concidered a wet location.
|
Electrical Rough-In | 2/28/2018 | 2/28/2018 | 2/28/2018 | P | PASS |
Rock A. Hudson
|
|
|
We are requesting a wall rough-in in the basement area for this afternoon. Our contact is Luke @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Prep kitchen #2 to right of door walls and hard lid rough in ok cover
|
Electrical Rough-In | 12/13/2017 | 12/14/2017 | 12/14/2017 | A | PART |
Rock A. Hudson
|
|
|
This inspection is for temporary occupancy of the partial prep room which failed the last inspection due to the BLD permit still under review. Our understanding is this would be resolved between the Architect and City today. Site Contact: Luke Hardy, ###-####. Phone #: ###-#### Inspection requested via web by Larry Looney No rough in needed. Created to note for ok occupy prep room A.
|
Rough-In Permanent Service | 12/12/2017 | 12/12/2017 | 12/12/2017 | P | PASS |
Rock A. Hudson
|
|
|
We are hoping for a Temporary Occupancy inspection for this afternoon. Our contact is Luke @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Unable to give temp occupancy due to BLD has been resubmitted for plan mod and is under review. 210.8(B)- All receptacles located in kitchen areas shall have GFCI protection. Walls in worm room rough in ok cover
|
Electrical Rough-In | 11/30/2017 | 11/30/2017 | 11/30/2017 | P | PASS |
Rock A. Hudson
|
|
|
We are requesting a rough-in inspection walls and ceiling for this afternoon. Our contact is Luke ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Prep room A homerun cove only rough in ok cover
|
Electrical Rough-In | 11/27/2017 | 11/28/2017 | 11/28/2017 | P | PART |
James Ady
|
|
|
We are requesting a partial rough-in inspection for the basement walls. Our contact is Luke at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Clint Tate Prep room A walls and lid minus home run cove on East side of room
|
Electrical Rough-In | 11/3/2017 | 11/3/2017 | 11/3/2017 | P | PASS |
Rock A. Hudson
|
|
|
Underfloor conduits rough in ok cover
|