Permit Information
Permit NumberELE17-03784
StatusFinaled
Name POWER PLUS INC
Site Address 1101 W FRONT ST
Project NameChamber of Commerce
Customer Number1490
ePlanReviewNo
Description
Alteration: Boise Metro Chamber of commerce, T.I. - electrical
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/27/20187/27/20187/27/2018PPASS
DetailsRock A. Hudson
George Morris is contact at ###-####. thank you. Phone #: ###-#### Inspection requested via web by Debby Pierce Final ok
Final1/16/20181/16/20181/16/2018PPART
DetailsRock A. Hudson
TCO Temp final Boise Chamber Commerce. Verify GFI drinking fountain and front reception desk. Phone #: ###-#### Inspection requested via web by Debby Pierce
Water heater disconnect shall be below 6'7". Furniture shall be complete for final.
TCO partial final ok
Final1/12/20181/12/20181/12/2018PFAIL
DetailsRock A. Hudson
At the end of the day if possible Phone #: ###-#### Inspection requested via web by Debby Pierce
Furniture connections shall be terminated or removed for TCO.
Circuit for millwork shall terminate in a box or wiring shall be complete once millwork in place.
210.8- Drinking fountains shall have GFCI protection.
Electrical Rough-In1/10/20181/10/20181/11/2018PPASS
DetailsRock A. Hudson
Ceiling rough-in. Rooms 108,138,109,110,134 Phone #: ###-#### Inspection requested via web by Debby Pierce
Discussed NEC 210.71 Meeting rooms. Due to code change year and 60 day grace period requirements for new code for meeting rooms receptacles will not be enforced.
Grid for rooms noted rough in ok cover
Electrical Rough-In1/8/20181/8/20181/8/2018PPASS
DetailsRock A. Hudson
Ceiling Inspection.

George Morris is the contact on site ###-#### Phone #: ###-#### Inspection requested via web by Debby Pierce
108, 109, 110, and138 has 2 luminaires not ready. Rest of grid rough in ok cover
Electrical Rough-In1/8/20181/8/20181/8/2018ANR
DetailsRock A. Hudson
Ceiling inspection Phone #: ###-#### Inspection requested via web by Debby Pierce
Complete seizmiz support of luminaires as per 300.11. Will recall when ready.
Electrical Rough-In1/5/20181/5/20181/5/2018PPART
DetailsJames Ady
Partial Drop ceiling only Conference room and offices on West side of South hall. only Areas listed ONLY ok to cover. Did not give go ahead to do any borders other than listed areas,
Electrical Rough-In1/4/20181/4/20181/4/2018PPASS
DetailsEric Story
Floor box rough-in Phone #: ###-#### Inspection requested via web by Debby Pierce
Floor boxes ok to cover, Talked about installing perimeter ceiling tiles A phone will be needed to main inspector in area 327.
Electrical Rough-In12/13/201712/13/201712/13/2017APASS
DetailsRock A. Hudson
Bathroom ceiling inspection Phone #: ###-#### Inspection requested via web by Debby Pierce
Bathroom drop ceilings rough in ok cover
Electrical Rough-In12/7/201712/8/201712/8/2017PPART
DetailsRock A. Hudson
Can lights above hard lid ceilings Phone #: ###-#### Inspection requested via web by Debby Pierce
Bathroom lids not ready, shall frame in accesses for junction boxes located above hardlids. Other drop lids rough in ok cover
Permanent Service12/6/201712/6/201712/6/2017PCANC
DetailsRock A. Hudson
Service inspection for MDP and MC Inspection requested via web by Debby Pierce
Wrong permit requested, service is associated with entire building. Needed
ELE16-04017
Electrical Rough-In11/28/201711/29/201711/29/2017PPASS
DetailsRock A. Hudson
Wall and ceiling rough-in Phone #: ###-#### Inspection requested via web by Debby Pierce
Vehicle blocked in due to all entrances closed up so landscaping around perimeter could be completed. Over 30 minutes before George was able to clear path. Will call to make sure entrance and exit will remain clear. Inspection will fail if access is not available.
Wall rough in ok cover
Conference11/20/201711/20/201711/20/2017PDONE
DetailsRock A. Hudson
HVAC FCU, clearances Phone #: ###-#### Inspection requested via web by Debby Pierce
Discussed access to control box on HVAC units mounting in ceiling areas.
NEC 110.26 states full 30"wide and 36" deep work space shall be present. As per Daryl Degrange a reduction of 24" wide and 18" deep shall be provided minimum for access. Where an individual can safely reach over walls or piping systems for access reach shall be 18" or less so as to not create a danger of over reach.
Electrical Rough-In11/9/201711/9/201711/9/2017PPASS
DetailsRock A. Hudson
Ceiling rough-in for exposed hallway entry Phone #: ###-#### Inspection requested via web by Debby Pierce
Discussed general contractor wanting to 1 side walls with drywall. This is not allowed except for firewalls and where needed for equipment. Electrical contractor will call for any wall cover needed.
Hallway and entry on east end of building ceiling to allow for insulation. Area noted rough in ok cover with insulation only.