Electrical Rough-In | 11/22/2017 | 11/22/2017 | 11/22/2017 | P | PASS |
James Ady
|
|
|
Solar rough in. Corrections made. Listing ok Rough in ok
|
Final | 11/21/2017 | 11/22/2017 | 11/22/2017 | A | PASS |
James Ady
|
|
|
Please call 30 min in advance so Shawn can meet you there. Thanks, Phone #: ###-#### Inspection requested via web by Kerri Hamilton Final ok
|
Final | 11/13/2017 | 11/14/2017 | 11/14/2017 | A | FAIL |
James Ady
|
|
|
Please contact Eva, the homeowner for access at ###-#### Phone #: ###-#### Inspection requested via web by Kerri Hamilton 690.13B PV systam disc shall be marked.690.31G PV system circuits shall be ran in metal raceway. 690.31G3 690.31G4. Raceway shall be marked every 10ft and shall use listed labeling. 690.43. PV equipment shall be bonded. Idaho power disc shall be "Knife Switch" style with external handle and shall be lockable.
|