Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE17-03962
StatusFinaled
Name JES ELECTRIC
Site Address 3100 N LAKEHARBOR LN Unit: 175
Project Name 
Customer Number2017-99
ePlanReviewNo
Description
New: Remove Existing Lights Add 11 New 2X2 Tr-offers, 20 Outlets And 15 Data Drops.. Useing Existing Branch Circuits
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/6/201712/7/201712/7/2017APASS
DetailsMark Moncarr
This Ia All Ready For A Final And Cieling Is Done Lock Box Code Is 4209. Please Call With Any Questions Or Concrns Thanks So Much Dave ###-#### Phone #: ###-#### Inspection requested via web by jason shifflett Ok final.
Electrical Rough-In11/21/201711/22/201711/22/2017APASS
DetailsMark Moncarr
This Is A Wall Inspection For Cover Only Ill Have The Ceiling Done Next Week.The Space Is Unoccupied And The Lock Box Code Is 4290. Please Call With Any Questions Or Concerns Thanks And Have A Happy Thanksgiving! Dave ###-#### Phone #: ###-#### Inspection requested via web by jason shifflett Ok cover. Conference room is 216 sq ft. 210.71(B)(2) states if it is over 215 it has to have floor outlet. With this small difference in floor space I will not require a floor outlet to be installed due to extensive cost for concrete work. Number of outlets required meets 210.52(A)(2).