Final | 3/9/2018 | 3/12/2018 | 3/12/2018 | A | PASS |
Rock A. Hudson
|
|
|
garage code 2824 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|
Final | 3/8/2018 | 3/9/2018 | 3/9/2018 | A | FAIL |
Rock A. Hudson
|
|
|
2824 garage code Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.3- Garage GFCI to left of panel shows open ground when tested. 210.23(A)(2)- Appliances fastened in place that exceed 50% of branch circuit shall be fed by a dedicated circuit. Microwave 1460 watts exceeds 50% of 20 amp branch circuit. Remove hood from circuit. 410.16(C)(1)- Incandescent or LED surface mount luminaires shall clear storage shelf by 12" minimum in master clothes closet.
|
Rough-In Permanent Service | 11/22/2017 | 11/24/2017 | 11/24/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn rough in ok p/s u/g n ok
|