Final | 1/12/2018 | 1/12/2018 | 1/12/2018 | A | PASS |
Tom Saunders
|
|
|
final for CO...corrections made...ok to final
|
Final | 1/10/2018 | 1/11/2018 | 1/11/2018 | A | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton... 1) dishwasher receptacle shall be located in the space adjacent to the space occupied by the dishwasher...receptacle shall be accessible.. 422.16(B)(2)6 & 7 2) remove GFI from fridge location...GFI shall be readily accessible...422.5(B)
|
Electrical Rough-In | 12/28/2017 | 12/29/2017 | 12/29/2017 | A | PASS |
Tom Saunders
|
|
|
Ceiling rough-in; need approval to drop ceiling tiles Phone #: ###-#### Inspection requested via web by Graham Estep...ceiling grid ok
|
Permanent Service | 12/12/2017 | 12/12/2017 | 12/12/2017 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton...p/s u/g meterpack ok..meter G location
|
Electrical Rough-In | 12/5/2017 | 12/6/2017 | 12/6/2017 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton...wall cover only ok
|