Permit Information
Permit NumberELE17-04117
StatusFinaled
Name UNITED ELECTRIC CONTRACTING
Site Address 1087 W RIVER ST Unit: 330
Project Name 
Customer NumberDSH-330
ePlanReviewNo
Description
Alteration: Tenant Improvement: Demo, Relocate lights & re-do switches; New recepts, 4-plex recepts, GFI recepts, and dedicated recepts/GFI per plans; tele/data per plan; 4 TV locations include power, data and cable box/conduit, no cabling or jacks; recessed can lig
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/27/20183/28/20183/28/2018PPASS
DetailsRock A. Hudson
please contact Matt Burns with any questions or concerns

Thank you and have a nice day! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Final ok
Electrical Rough-In3/21/20183/22/20183/22/2018APASS
DetailsRock A. Hudson
Ceiling Inspection

Please contact Matt Bruns @ ###-#### with any questions Phone #: ###-#### Inspection requested via web by JENNY EMEL
Phase 2 grid rough in ok cover
Electrical Rough-In2/28/20182/28/20182/28/2018PPASS
DetailsRock A. Hudson
Please contact Matt Bruns with any questions

Thank you! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Offices 312, 313, 314, 315, conference rm 316, reception 322, admin 323, 324, work rm 325 and break rm door 326 B wall rough in ok cover
Final2/5/20182/6/20182/6/2018APART
DetailsRock A. Hudson
Request is for a final inspection for Phase I of this project. Matt Bruns will meet you at the site.

Thank you! Phone #: ###-#### Inspection requested via web by JENNY EMEL
210.71-Conference rooms floor receptacles not in yet.
IECC 2015 required C405.2.1- Occupancy sencors required in all private offices, break rooms, some offices not in.
TCO for phase 1- 301 thru 311, 326 thru 328 OK
Conference2/5/20182/5/20182/5/2018PDONE
DetailsRock A. Hudson
REQUESTING A TELEPHONE CONFERENCE CONCERNING QUESTIONS ON FINAL FOR THE FIRST PHASE OF THIS PROJECT - NO ON-SITE VISIT REQUIRED

PLEASE CALL MATT BRUNS @###-####

THANK YOU VERY MUCH AND HAVE A VERY WUNDERFUL DAY!
Phone #: ###-#### Inspection requested via web by JENNY EMEL
Discussed the need and procedure for temp or partial final for phase 1 of remodel. Informed to request a final inspection with detailed notes as to which areas needed for TCO and that I would note a partial final for the areas listed.
Electrical Rough-In1/12/20181/16/20181/16/2018APASS
DetailsRock A. Hudson
Ceiling Inspection

Contact Matt Bruns with any Questions Phone #: ###-#### Inspection requested via web by JENNY EMEL
Grid rough in ok cover
Electrical Rough-In12/6/201712/7/201712/7/2017APASS
DetailsRock A. Hudson
Please contact Matt Bruns with any questions

This is a wall rough-in inspection

Thank you and have a nice day! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Called contact to discuss 210.71 he stated he was aware of requirements. Conf. rm 302 is 228 sq.ft., 6 receptacles, rm 304 is 303 sq.ft., 7 receptacles, rm 311 is 235 sq.ft. 6 receptacles, rm 316 part of phase 2. Rooms 301 thru 311 and 326 thru 328 wall rough in ok cover