Permit Information
Permit NumberELE17-04131
StatusFinaled
Name TASKER ELECTRICAL CONSTRUCTION INC
Site Address 6663 S EISENMAN RD
Project Name 
Customer Number 
ePlanReviewNo
Description
New: complete electrical for Warehouse C;gear, lights, fire alarm, &site lighting
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/17/20187/18/20187/18/2018APASS
DetailsJames Ady
Tobias is the site contact. Phone #: ###-#### Inspection requested via web by Stacie Tasker Final ok
Final7/16/20187/17/20187/17/2018APART
DetailsJames Ady
Tobias is the site contact. Phone #: ###-#### Inspection requested via web by Stacie Tasker Missing panel schedules on 480v panels.
Final7/16/20187/16/20187/16/2018PFAIL
DetailsJames Ady
Tobias is the site contact. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker W/P Riser room Dead, Front office receps dead. Back of wearhouse left of roll up door recep dead, occ sensors in offices, Disc. on mini splits with proper oc protection.
Final7/9/20187/10/20187/10/2018ANR
DetailsJames Ady
Tobias is the site contact. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Office areas attached to core and shell need copleted as well as all wearhouse lighting not in leased areas and not being changed by tenant
Electrical Rough-In7/3/20187/3/20187/3/2018PPASS
DetailsJames Ady
We need a ceiling cover, please.
Tobias is the site contact.
Thank you Phone #: ###-#### Inspection requested via web by Stacie Tasker Ceiling ok to cover
Electrical Rough-In6/29/20187/2/20187/2/2018AFAIL
DetailsJames Ady
we would like to request an early morning inspection for a ceiling cover. Tobias is the site contact.
Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker 336.12 2. TC cable shall not be ran outside of a raceway or cable tray except from tray to equipment.
Electrical Rough-In6/6/20186/6/20186/6/2018PPASS
DetailsJames Ady
Tobias is the site contact Phone #: ###-#### Inspection requested via web by Stacie Tasker added walls in south office areas only ok to cover
Rough-In Permanent Service5/30/20185/31/20185/31/2018ACANC
DetailsJames Ady
We need an inspection for South end of C.
Tobias is the site contact. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker
Electrical Rough-In5/31/20185/31/20185/31/2018PPASS
DetailsJames Ady
We need an inspection for South end of C.
Tobias is the site contact. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker ok to cover walls only
Permanent Service5/25/20185/25/20185/25/2018PPASS
DetailsJames Ady
Tobias is the site contact. Phone #: ###-#### Inspection requested via web by Stacie Tasker p/s u/g n ok
Electrical Rough-In5/21/20185/21/20185/21/2018PPASS
DetailsJames Ady
We need a soffit inspection. Tobias is the site contact, Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker North canopy not ready. All others ok to cover
Electrical Rough-In5/9/20185/9/20185/9/2018PPASS
DetailsJames Ady
We need a wall cover for late afternoon if possible. Tobias is the site contact.
Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Front office demizing wall
Electrical Rough-In5/4/20185/4/20185/4/2018PPASS
DetailsRock A. Hudson
We need a wall rough. Tobias is the site contact.
Thank you Phone #: ###-#### Inspection requested via web by Stacie Tasker
Fire pump room wall rough in ok cover
Electrical Rough-In3/15/20183/16/20183/16/2018PCANC
DetailsJames Ady
We need a underground inspection. Tobias is the site contact. Phone #: ###-#### Inspection requested via web by Stacie Tasker
Electrical Rough-In3/14/20183/15/20183/15/2018PPASS
DetailsJames Ady
We need an underground inspection.
Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker pour back along perimeter of building only ok to cover
Electrical Rough-In3/6/20183/7/20183/7/2018APASS
DetailsJames Ady
We need an underground inspection, please.
Site contact is Tobias. Phone #: ###-#### Inspection requested via web by Stacie Tasker perrimeter underground ok to cover
Electrical Rough-In12/22/201712/22/201712/22/2017PPASS
DetailsJames Ady
We need a ufer inspection. Dave is the site contact. Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker ufer only ok
Electrical Rough-In12/8/201712/11/201712/12/2017PPASS
DetailsDaryl DeGrange
We need an underground inspection. Tobias is the site contact.
Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Rough-in ok cover service feeder raceways under slab, south half of Building C