Final | 4/25/2018 | 4/25/2018 | 4/25/2018 | A | PASS |
Tom Saunders
|
|
|
ok to final
|
Final | 4/24/2018 | 4/24/2018 | 4/24/2018 | P | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson...
lights in closet shall have completely enclosed light source...LED...410.16
|
Final | 4/18/2018 | 4/19/2018 | 4/19/2018 | P | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson... 1..A/C disconnects need circuit labelling 2..hot/neutral reverse garage GFI 3..exposed wires in patio ceiling...wires need safed off and blank installed 4..cans in master closet need to be rated for location...enclosed lamp 5..spark rings need installed in bath/pool room 6..wires exposed to physical damage at pop up outlets in corner of kitchen 7..cans in bath/pool room shall be rated for damp location 8..bath/pool room exhaust fan shall have GFI protection 9..bath/pool rm switches and over head all needs GFI protection...damp location rated area...full room
|
Rough-In Permanent Service | 1/15/2018 | 1/16/2018 | 1/16/2018 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson...rough ok to cover...p/s u/g new ok
|