Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE17-04148
StatusFinaled
Name ROBERTSON ELECTRIC
Site Address 6001 W RANDOLPH DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: Complete wiring of a single family home
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/25/20184/25/20184/25/2018APASS
DetailsTom Saunders
ok to final
Final4/24/20184/24/20184/24/2018PFAIL
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Zane Robertson...

lights in closet shall have completely enclosed light source...LED...410.16
Final4/18/20184/19/20184/19/2018PFAIL
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Zane Robertson...
1..A/C disconnects need circuit labelling
2..hot/neutral reverse garage GFI
3..exposed wires in patio ceiling...wires need safed off and blank installed
4..cans in master closet need to be rated for location...enclosed lamp
5..spark rings need installed in bath/pool room
6..wires exposed to physical damage at pop up outlets in corner of kitchen
7..cans in bath/pool room shall be rated for damp location
8..bath/pool room exhaust fan shall have GFI protection
9..bath/pool rm switches and over head all needs GFI protection...damp location rated area...full room
Rough-In Permanent Service1/15/20181/16/20181/16/2018PPASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Zane Robertson...rough ok to cover...p/s u/g new ok