Permit Information
Permit NumberELE17-04191
StatusFinaled
Name 45TH PARALLEL ELECTRIC LLC
Site Address 2454 N MILWAUKEE ST
Project Name 
Customer Number33033
ePlanReviewNo
Description
Alteration: tenant improvement
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/9/20182/9/20182/9/2018PPASS
DetailsTom Saunders
call ###-#### for access Phone #: ###-#### Inspection requested via web by David Nelson...corrections made...ok to final
Final2/7/20182/8/20182/8/2018AFAIL
DetailsTom Saunders
access key is on the North rock formation to the right of the doors on a red rock at eye level, call ###-#### Phone #: ###-#### Inspection requested via web by David Nelson..
1.outlet within 6' of sink shall have GFCI protectrion
2. OCPD on A/C is too large
3. A/C shall be labelled for identification
4. plates need installed on switch and outlets inside hearing booth...light covers installed
5. service outlet for A/Cs has no power..check GFCI protection
Rough-In Permanent Service12/18/201712/19/201712/19/2017APASS
DetailsTom Saunders
Unit should be open by 9:00 by general contractor. Phone #: ###-#### Inspection requested via web by David Nelson...p/s u/g new ok...rough in ok to cover
Permanent Service12/14/201712/15/201712/15/2017AFAIL
DetailsEric Story
Service inspection so service can be re-energized. Unit should be open by 9:00 by general contractor. Phone #: ###-#### Inspection requested via web by David Nelson
110.24 AFC calculation required proir to service being energized.
Need to verify main bonding jumper in main service gear no access inside to see it