Final | 6/29/2018 | 7/2/2018 | 7/2/2018 | P | PASS |
James Ady
|
|
|
Jeff Phone #: ###-#### Corrections made final ok
|
Final | 2/27/2018 | 3/1/2018 | 3/1/2018 | A | NH |
Eric Story
|
|
|
Any questions please call Louis at ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller No body home
|
Final | 2/6/2018 | 2/12/2018 | 2/12/2018 | A | FAIL |
James Ady
|
|
|
Any questions please call louis at ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller 334.12(B)(4)- NM cables shall not be installed In wet or damp locations. Inside outdoor or underground raceways concidered wet location
|
Final | 12/28/2017 | 12/29/2017 | 12/29/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Any questions please call Louis at ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller 300.4(B)(1)- Nonmetallic-Sheathed Cable. In both exposed and concealed locations where nonmetallic-sheathed cables pass through either factory- or field-punched, cut, or drilled slots or holes in metal members, the cable shall be protected by listed bushings or listed grommets covering all metal edges that are securely fastened in the opening prior to installation of the cable. Where NM enters panel. 334.12(B)(4)- NM cables shall not be installed In wet or damp locations. Inside outdoor or underground raceways concidered wet location Owner had to leave, put correction on meter base.
|