Permit Information
Permit NumberELE18-00402
StatusFinaled
Name LARSON ELECTRIC
Site Address 410 S WILSON ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Re-wire 800 as ft house
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/19/20184/19/20184/19/2018PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Nick Larson
Final ok
Final4/18/20184/18/20184/18/2018PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Nick Larson
406.6- Receptacles installed on a ungrounded circuit shall have GFCI protection or a 2 wire receptacle installed.
406.12- Island receptacle shall be tamper resistant type.
422.30- Hood shall have a disconnecting means, switch on unit did not operate.
Final4/16/20184/17/20184/17/2018PNH
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Nick Larson
Residence lived in must have someone here for inspection. Shall recall
Electrical Rough-In2/5/20182/5/20182/5/2018APASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Nick Larson Corrections made rough in ok
Electrical Rough-In1/31/20182/2/20182/2/2018PFAIL
DetailsEric Story
Call for code Phone #: ###-#### Inspection requested via web by Nick Larson
300 Type NM cable shall not be installed within 1 1/4 of framing member
Temp power shall be GFCI protected