Permit Information
Permit NumberELE18-00603
StatusFinaled
Name QUALITY ELECTRIC INC
Site Address 160 N 8TH ST
Project Name 
Customer Number18210
ePlanReviewNo
Description
New: Furnish and install electrical system per approved plans
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/22/20185/23/20185/23/2018APASS
DetailsRock A. Hudson
Contact is Shane Korte Phone #: ###-#### Inspection requested via web by Scott Campbell Final ok
Final5/21/20185/22/20185/22/2018AFAIL
DetailsRock A. Hudson
Contact is Shane Korte Phone #: ###-#### Inspection requested via web by Scott Campbell
210.8(B)- All receptacle outlets located with in 6' of a sink shall have GFCI protection. 2 gang above counter in serving area.
422.30- Each appliance shall have a disconnecting means. 60 map fryer, hood circuits.
400.12- Flexible cords shall not be installed above grid. Sign.
Electrical Rough-In3/1/20183/2/20183/2/2018APASS
DetailsRock A. Hudson
Contact is Jim Noll - wall rough-in inspection Phone #: ###-#### Inspection requested via web by Scott Campbell
Walls and seating area so grid can be painted. Few open boxes above this grid tha will be checked next trip. Rough in noted ok cover