ELE-Aging Inspection | 7/29/2020 | 7/29/2020 | 7/29/2020 | | PEND |
Daryl DeGrange
|
|
|
This permit is still open with the City of Boise. Please call 208 ###-#### with progress report or any questions. If this job is complete, please schedule an final inspection online Thank you!
|
ELE-Aging Inspection | 4/29/2020 | 4/29/2020 | 4/29/2020 | | FAIL |
Daryl DeGrange
|
|
|
Pursuant of contacting aging permit applicants is on hold until required Social Distancing has been removed.
|
Final | 3/15/2018 | 3/16/2018 | 3/16/2018 | P | FAIL |
James Ady
|
|
|
John Phone #: ###-#### tryed several times to reach contact. No answer. Full voice mail box. Need pics sent as discussed of panel schedule and missing KO seal.
|
Final | 3/14/2018 | 3/15/2018 | 3/15/2018 | A | FAIL |
James Ady
|
|
|
go to lobby and ask for Mark Evens Phone #: ###-#### Correct address is 2600 Amity. 110.12A All unused openings shall be closed.(2 gang bellbox below panel. 1/2in KO missing on right side.) 408.4A Circuit directory shall be clearly and correctly marked
|