Permit Information
Permit NumberELE18-00763
StatusFinaled
Name VANZANDT ELECTRIC
Site Address 1915 E RIDGECREST DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: Wire house
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/1/20192/1/20192/1/2019PPASS
DetailsJames Ady
Please call for access Phone #: ###-#### Inspection requested via web by John VanZandt Corrections made final ok
Final1/30/20191/31/20191/31/2019AFAIL
DetailsRock A. Hudson
Please call for access Phone #: ###-#### Inspection requested via web by John VanZandt 210.8(A)(1)- All receptacles installed to serve bathroom basins shall have GFCI protection. All basement bathroom receptacles.
210.8(A)(2)- All 15 and 20 amp 120 volt receptacle outlets installed in a garage shall have GFCI protection. Receptacle located on warm wall.
210.52(C)- In kitchens, pantries, and similar areas receptacle outlets installed to serve counter top surfaces shall be installed so no point measured along wall line is more than 24" from a receptacle.
250.122- Minimum equipment grounding conductor for a 30 amp circuit shall not be smaller than #10. #12 installed in AC whip.
Electrical Rough-In8/27/20188/27/20188/27/2018PPASS
DetailsRock A. Hudson
Floor heat Insp Phone #: ###-#### Inspection requested via web by John VanZandt
Rough in ok cover
Rough-In Permanent Service2/28/20183/1/20183/1/2018APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by John VanZandt
Class 2 used for pull wire, no changes to each side of fire place, receptacles in pantry are GFCI devices for wire mold.
Rough in ok cover p/s u/g n ok
Rough-In Permanent Service2/27/20182/28/20182/28/2018AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by John VanZandt
110.3- As per manufacturers instructions furnace shall have a minimum of 12 ga branch circuit.
210.52(A)(2)- Cabinet spec not found. Possible wall space each side of fireplace.
210.52(C)(1)- If receptacle located in pantry serve counter top space no point on counter shall be more than 24" from a receptacle.
300.15- Master bath stool fan not made up.
300.3- 600 volt and class 2 in same box for floor heat. Both shall have rating to cover voltage present in box.
408.3(A)(2)- Service conductor terminations shall have barriers installed.
* Meter load terminations shall be lower lugs. Upper for incoming conductors.