Permit Information
Permit NumberELE18-00810
StatusFinaled
Name MULTI STATE ELECTRIC
Site Address 1150 N CLOVERDALE RD
Project NameCloverdale Funeral Maintenance
Customer Number 
ePlanReviewNo
Description
New: New service, new lighting, and new outlets with HVAC hook ups
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final6/7/20186/8/20186/8/2018APASS
DetailsTom Saunders
Everything should be taken care of thanks have a great day Brad Phone #: ###-#### Inspection requested via web by Brad Baker...corrections made...ok to final
Final6/4/20186/5/20186/5/2018AFAIL
DetailsTom Saunders
should be open Phone #: ###-#### Inspection requested via web by Brad Baker...
1. bath instahot needs to be a 30A circuit per manufacturers rating...110.3
2. panel labelling needs completed...408.4
3. outlets within 6' of sink shall have GFCI protection...breakroom future sink..210.8(B)(5)
4. west wall GFCI has no power...unlabelled circuit in panel??
Electrical Rough-In4/19/20184/19/20184/19/2018APASS
DetailsJames Ady
Reinspect of interior walls corrections made rough in ok
Electrical Rough-In4/17/20184/18/20184/18/2018AFAIL
DetailsJames Ady
requesting an inspection for cover framed areas and warehouse, warehouse will be exposed out of the wall areas, they are going to insulate and cover with white plastic vinyl Phone #: ###-#### Inspection requested via web by Brad Baker 250.68A. All mechanical elements used to attach GEC and Bonding jumper shall be accessible. ( UFER and building steel.)
Permanent Service3/23/20183/26/20183/26/2018APASS
DetailsRock A. Hudson
We have installed the permanent service by passing setting a temporary pole please call me. We have put a temporary protection cover over it as the roof is being installed this week Phone #: ###-#### Inspection requested via web by Brad Baker
250.8- Connection to building steel shall be made with a machine screw not self tapping button head screw. Ufer in place.
408.3(A)(2)- Service termination lugs shall have barriers installed to prevent accidental contact. Contractor to complete 3/26.
Easy corrections. p/s o/h n ok
Electrical Rough-In3/4/20183/5/20183/5/2018APASS
DetailsTom Saunders
requesting an inspection for under slab PVC work thank you Phone #: ###-#### Inspection requested via web by Brad Baker...ok to cover