Final | 4/22/2018 | 4/23/2018 | 4/23/2018 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by Eddy Udry Ok final. Corrections made.
|
Final | 4/16/2018 | 4/16/2018 | 4/16/2018 | P | FAIL |
Mark Moncarr
|
|
|
Use contractor box on porch.. # is 5544 The Irene street porch Thanks Inspection requested via web by Eddy Udry 1. GFI not tamper resistant in W bed. 2. ARC fault recept installed in other bed, needs to be GFI. Also recept has no power. 3. Faceplates need to be of adequate strength to withstand foot traffic. Metal faceplates needed.
|
Final | 4/13/2018 | 4/13/2018 | 4/13/2018 | P | FAIL |
Mark Moncarr
|
|
|
Home is vacant Contractor Lock box is on the south porch (Irene street side) # is 5544 Phone #: ###-#### Inspection requested via web by Eddy Udry 1. Label Panel 2. P-8 needed for micro recept. 3. Lockout for D/W. 4. I know it wasnt in the scope of work, but it is a life safety issue. Changed out the few floor outlets in bedrooms to GFI's or GFI brkr.
|