Final | 5/14/2018 | 5/14/2018 | 5/14/2018 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Ron Zimmerman Final ok
|
Final | 5/10/2018 | 5/10/2018 | 5/10/2018 | P | PART |
Rock A. Hudson
|
|
|
Except cubicles Phone #: ###-#### Inspection requested via web by Ron Zimmerman Corrections not complete. EMT above trusses existing from original install and no wiring added. OK to remain. 300.4(E)- MC cables shall not run over trusses in shallow grooves. Only exception is for IMC and RMC can be installed with in 1 1/2" of lowest part of roof decking. Contractor will either move MC cables or protect with IMC or heavier shield. All located above trusses. Will check on final. Signed card TCO
|
Final | 5/8/2018 | 5/8/2018 | 5/8/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Final with exception to cubacle hookups Phone #: ###-#### Inspection requested via web by Ron Zimmerman Drinking fountain existing GFCI is located inside left unit. Vending machine going in break room no GFI at time of inspection. Listing confirmed on furniture however... Contractor stated all new wiring installed for lighting. 300.4(E)- Cables, raceways, and boxes shall be installed so there is not less than 1 1/2" from lowest surface of roof decking.
|
Electrical Rough-In | 4/24/2018 | 4/24/2018 | 4/24/2018 | A | PASS |
Tom Saunders
|
|
|
Ceiling cover Phone #: ###-#### Inspection requested via web by Ron Zimmerman...breakroom and meeting room grid ok to cover
|
Electrical Rough-In | 3/27/2018 | 3/27/2018 | 3/27/2018 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Ron Zimmerman...inspection was for part demo and addition of misc outlets fished in or wiring needing cover...ok
|