Permit Information
Permit NumberELE18-01049
StatusFinaled
Name BEACON ELECTRIC
Site Address 12754 W LASALLE ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: demo &new lighting throughout, re-hook cubicles some wall demo & new walls
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/14/20185/14/20185/14/2018APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Ron Zimmerman
Final ok
Final5/10/20185/10/20185/10/2018PPART
DetailsRock A. Hudson
Except cubicles Phone #: ###-#### Inspection requested via web by Ron Zimmerman
Corrections not complete. EMT above trusses existing from original install and no wiring added. OK to remain.
300.4(E)- MC cables shall not run over trusses in shallow grooves. Only exception is for IMC and RMC can be installed with in 1 1/2" of lowest part of roof decking.
Contractor will either move MC cables or protect with IMC or heavier shield.
All located above trusses. Will check on final.
Signed card TCO
Final5/8/20185/8/20185/8/2018PFAIL
DetailsRock A. Hudson
Final with exception to cubacle hookups Phone #: ###-#### Inspection requested via web by Ron Zimmerman
Drinking fountain existing GFCI is located inside left unit. Vending machine going in break room no GFI at time of inspection.
Listing confirmed on furniture however... Contractor stated all new wiring installed for lighting.
300.4(E)- Cables, raceways, and boxes shall be installed so there is not less than 1 1/2" from lowest surface of roof decking.
Electrical Rough-In4/24/20184/24/20184/24/2018APASS
DetailsTom Saunders
Ceiling cover Phone #: ###-#### Inspection requested via web by Ron Zimmerman...breakroom and meeting room grid ok to cover
Electrical Rough-In3/27/20183/27/20183/27/2018PPASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Ron Zimmerman...inspection was for part demo and addition of misc outlets fished in or wiring needing cover...ok