Final | 7/24/2018 | 7/24/2018 | 7/24/2018 | P | PASS |
James Ady
|
|
|
Cruz Phone #: ###-#### final ok
|
Electrical Rough-In | 4/5/2018 | 4/6/2018 | 4/6/2018 | A | PASS |
James Ady
|
|
|
Cruz Phone #: ###-#### corrections made Kitchen, storage areas only ok to cover
|
Electrical Rough-In | 4/2/2018 | 4/3/2018 | 4/3/2018 | A | FAIL |
James Ady
|
|
|
best between 10 and 1230, Cruz Blanco Phone #: ###-#### 210.52C1 Counter receps shall be installed so that no point measured along the wall line is more than 24in from a recep. 240.4D3 14 gauge shall not be installed on a 20 circuit. ( Kitchen )
|
Conference | 3/23/2018 | 3/26/2018 | 3/26/2018 | A | PASS |
James Ady
|
|
|
Cruz Phone #: ###-#### talked about kitchen lay out, Circuitry, Outside lights and recep required, owner has Homeowner hand out.
|