Permit Information
Permit NumberELE18-01195
StatusFinaled
Name LOTT ELECTRIC INC
Site Address 109 S 4TH ST
Project Name 
Customer NumberDesignWork
ePlanReviewNo
Description
Alteration: Tenant improvement: conduit and wiring for a complete electrical system. Installation of all fixtures.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/9/20188/9/20188/9/2018PPASS
DetailsEric Story
Final inspection please. Have a bless weekend! Phone #: ###-#### Inspection requested via web by Kyle Lott
Final ok card signed
Final8/8/20188/9/20188/8/2018ACANC
DetailsRock A. Hudson
Final inspection please. Have a bless day! Phone #: ###-#### >> Inspection requested via web by Kyle Lott Inspection cancelled from web by: Kyle Lott
Electrical Rough-In6/14/20186/14/20186/14/2018APASS
DetailsMark Moncarr
Rough in Entry Soffet please. Thank you. Phone #: ###-#### Inspection requested via web by Kyle Lott Ok cover entry soffit.
Electrical Rough-In5/2/20185/2/20185/2/2018PPASS
DetailsRock A. Hudson
Lighting assembly inspection please. Thank you. Have a bless Wednesday! Phone #: ###-#### Inspection requested via web by Kyle Lott
2 clouds will have access panels for junction boxes located above, took pictures. Ceiling rough in ok cover
Electrical Rough-In5/1/20185/1/20185/1/2018PFAIL
DetailsRock A. Hudson
Ceiling inspection please. Have a bless week! Phone #: ###-#### Inspection requested via web by Kyle Lott
110.14- Splice points shall be accessible. 2 boxes located above clouds.
300.4- MC shall be secured 1 1/4" from framing surface.
314.23- Boxes hanging out of cloud shall be securely mounted to structure.
Electrical Rough-In4/30/20184/30/20184/30/2018PCANC
DetailsRock A. Hudson
Ceiling inspection please. Have a bless week! Lott Electric INC Phone #: ###-#### >> Inspection requested via web by Kyle Lott Inspection cancelled from web by: Kyle Lott
Electrical Rough-In4/11/20184/12/20184/12/2018APASS
DetailsRock A. Hudson
Wall cover please. Phone #: ###-#### Inspection requested via web by Kyle Lott
Wall rough in ok cover
Electrical Rough-In4/10/20184/10/20184/10/2018PFAIL
DetailsRock A. Hudson
Wall cover please Phone #: ###-#### Inspection requested via web by Kyle Lott
300.4- MC run thru bored holes that do not maintain 1 1/4" from framing surface shall be protected from damage.
300.4- MC shall not be secured with in 1 1/4" from faming surface.
314.17- Unused knockouts shall be closed by approved means.
362.30- ENT shall be secured at intervals not to exceed 3' and shall be secured with in 3' of terminations.
590.6- All temp power used for construction shall have GFCI protection.