Final | 12/20/2018 | 12/20/2018 | 12/20/2018 | P | PASS |
Mark Moncarr
|
|
|
Please give me a call 30 minutes in advance so I can meet on site. Thank you Phone #: ###-#### Inspection requested via web by Casey Fouts Ok final. Contractor was onsite. Corrections were made.
|
Final | 12/18/2018 | 12/19/2018 | 12/19/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Please call 30min in advance so I can meet on site with you. Phone #: ###-#### Inspection requested via web by Casey Fouts 210.8- GFCI protection shall be provided for all 120 volt receptacle outlets up to 50 amp and other than 120 volt receptacles up to 100 amp. 300.11- Luminaires located in kitchen areas shall be supported independant of grid 300.15- Bath fan hanging from ceiling with splice not contained in a box. All aplices shall be contained in a box or enclosure. 422.31- A disconnecting means shall be provided for a appliances rated over 300 VA that shall be located with in 50' and with in sight of appliance. * All electrical power associated with hood shall be connected to ansil system to disconnect power in case of fire.
|
Electrical Rough-In | 4/30/2018 | 5/1/2018 | 5/1/2018 | A | PASS |
Rock A. Hudson
|
|
|
Please call 30min in advance to ensure access. Phone #: ###-#### Inspection requested via web by Casey Fouts Check above grid for open boxes or old luminaires. Walls rough in ok cover
|