Alteration: Tennant improvement
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/20/201812/20/201812/20/2018PPASS
DetailsMark Moncarr
Please give me a call 30 minutes in advance so I can meet on site. Thank you Phone #: ###-#### Inspection requested via web by Casey Fouts Ok final. Contractor was onsite. Corrections were made.
Final12/18/201812/19/201812/19/2018AFAIL
DetailsRock A. Hudson
Please call 30min in advance so I can meet on site with you. Phone #: ###-#### Inspection requested via web by Casey Fouts
210.8- GFCI protection shall be provided for all 120 volt receptacle outlets up to 50 amp and other than 120 volt receptacles up to 100 amp.
300.11- Luminaires located in kitchen areas shall be supported independant of grid
300.15- Bath fan hanging from ceiling with splice not contained in a box. All aplices shall be contained in a box or enclosure.
422.31- A disconnecting means shall be provided for a appliances rated over 300 VA that shall be located with in 50' and with in sight of appliance.
* All electrical power associated with hood shall be connected to ansil system to disconnect power in case of fire.
Electrical Rough-In4/30/20185/1/20185/1/2018APASS
DetailsRock A. Hudson
Please call 30min in advance to ensure access. Phone #: ###-#### Inspection requested via web by Casey Fouts
Check above grid for open boxes or old luminaires. Walls rough in ok cover