Final | 6/9/2020 | 6/9/2020 | 6/9/2020 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson Corrections made final ok
|
Final | 6/2/2020 | 6/3/2020 | 6/3/2020 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson 300.9 Interior of Raceways in wet locations, shall be cosidered wet location. 334.12 NM cable shall not be installed in wet location. (NM cable installed in flex from crawl to disc, and from Disc. to Condensor
|
ELE-Aging Inspection | 5/21/2020 | 5/21/2020 | 5/21/2020 | | FAIL |
Daryl DeGrange
|
|
|
Permit lacking final inspection
|