Permit Information
Permit NumberELE18-01573
StatusFinaled
Name R M E INC
Site Address 350 N 9TH ST Unit: 301
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration: Install power, Lighting and HVAC per drawings
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/20/20187/20/20187/20/2018PPASS
DetailsJames Ady
Von is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Final ok
Final6/25/20186/26/20186/26/2018APART
DetailsJames Ady
Please call Von 1/2 prior to arrival. Phone #: ###-#### Inspection requested via web by Buster Bowen Need Exit sign over back door and Lock out on disposal. Temp only ok
Electrical Rough-In6/12/20186/12/20186/12/2018APASS
DetailsRock A. Hudson
Ceiling cover. Von is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Grid rough in ok cover
Electrical Rough-In6/11/20186/11/20186/11/2018AFAIL
DetailsRock A. Hudson
Ceiling cover. Von is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
300.15- MC cable shall terminate in a box. 1 area behind reception 1 in office out of wall.
300.11- MC and other cable shall be supported insependant of grid. Fixture whip and low volt.
Electrical Rough-In4/25/20184/26/20184/26/2018APASS
DetailsRock A. Hudson
Wall Cover. Von is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Wall rough in ok cover