Final | 5/2/2018 | 5/3/2018 | 5/3/2018 | A | PASS |
James Ady
|
|
|
Changed the wire in conduit to meet wet location requirements. Strapped the conduit within 12” of box. Phone #: ###-#### Inspection requested via web by Jake Cutler Final ok
|
Final | 4/30/2018 | 5/1/2018 | 5/1/2018 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jake Cutler 300.9 Raceways in wet locations, Where raceways are installed in wet locations abovegrade, the interior of the raceway shall be considered to be wet location. 334.12B4. NM cable shall not be ran in wet location. 356.30 1 Liquidtight conduit shall be secured every 3ft and within 12in of every junction.
|