Final | 7/5/2018 | 7/5/2018 | 7/5/2018 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Robert Murray Final ok
|
Rough-In Permanent Service | 5/4/2018 | 5/4/2018 | 5/4/2018 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Robert Murray....rough ok to cover...p/s u/g new ok
|
Rough-In Permanent Service | 5/2/2018 | 5/3/2018 | 5/3/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Robert Murray 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing suface they shall be protected from damage by nail plates. Garage 10-2 rt of panel, above garage switches, above pantry switch, entry corner. 300.15- Wall wiring shall terminate in a box. Master stool bath fan not made up.
|