Final | 8/8/2018 | 8/8/2018 | 8/8/2018 | P | PASS |
Eric Story
|
|
|
Von. Phone #: ###-#### Inspection requested via web by Sean DeLacy Final ok
|
Electrical Rough-In | 7/11/2018 | 7/11/2018 | 7/11/2018 | A | PASS |
Eric Story
|
|
|
Von. Underground. Phone #: ###-#### Inspection requested via web by Sean DeLacy East end U/G ok to cover
|
Permanent Service | 6/29/2018 | 6/29/2018 | 6/29/2018 | A | PASS |
Rock A. Hudson
|
|
|
Von Phone #: ###-#### Inspection requested via web by Sean DeLacy Available fault current posted inside panel door. 18,722 amps highest availble on 25k rated main. p/s u/g n ok
|
Permanent Service | 6/28/2018 | 6/28/2018 | 6/28/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Von. Phone #: ###-#### Inspection requested via web by Sean DeLacy Located on back of liquor store. 110.24- Available fault current shall be posted prior to inspection with value and date calculated. 250.92(B)- Service equipment bonding, metal underground service lateral conduit shall both be bonded where they enter thru concentric knock outs.
|
Electrical Rough-In | 6/5/2018 | 6/5/2018 | 6/5/2018 | A | PASS |
Eric Story
|
|
|
Von. Uffer ground. Phone #: ###-#### Inspection requested via web by Sean DeLacy Uffer only on existing building ok to cover
|
Electrical Rough-In | 5/31/2018 | 5/31/2018 | 5/31/2018 | P | PASS |
Eric Story
|
|
|
Von. Underground. Phone #: ###-#### Inspection requested via web by Sean DeLacy S parking lot area ok to cover
|
Electrical Rough-In | 5/11/2018 | 5/11/2018 | 5/11/2018 | P | PASS |
Eric Story
|
|
|
Von. Underground cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy Part 1 of u/g for parking lot on east ok to cover
|