Permit Information
Permit NumberELE18-01929
StatusFinaled
Name BOISE BASIN ELECTRIC
Site Address 413 W JEFFERSON ST
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: Replaced feeders for existing 200 amp service, installed grounding for existing service, repaired wiring feeders to (2) apartments from fire.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/15/20198/16/20198/16/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
Permanent Service7/16/20197/16/20197/16/2019PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Alan Lusk p/s o/h rec ok
Final2/15/20192/20/20192/20/2019PPART
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Alan Lusk
110.8, 11,27(B), 300.3(A)- Exposed conductors running in and out of meter bases shall be installed in a recognized wiring method of chapter 3.
230.70(A)(1)- Main disconnecting means of service shall be on exterior of building or immediately on inside.
BCC 4 05 31(C)- Unfused conductors shall not enter a structure unless underground fed with a max of 4 1/2' in length.
240.24- Over current devices shall not be installed over stairs.
Service reconnect was granted on temporary basis so other tenants would not be without power for an extended period of time.
60 amp feeds to each apartment ok to remain if no changes done to apartments.
Complete service change is required.
Unit 4 tested ok. TCO ok
Final1/31/20191/31/20191/31/2019PNH
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Alan Lusk
All areas locked. Unit 4 looks lived in. Reschedule when accessible.
Electrical Rough-In7/16/20187/16/20187/16/2018PPASS
DetailsRock A. Hudson
Only a few walls opened up in kitchen only. Rough in ok cover
Electrical Rough-In7/16/20187/16/20187/16/2018PFAIL
DetailsRock A. Hudson
Unit #4 - Code 0140 Phone #: ###-#### Inspection requested via web by Alan Lusk
Lock box on rail on exterior, not sure which unit is unit 4. Have door identified and recall.
Permanent Service5/23/20185/23/20185/23/2018PPASS
DetailsRock A. Hudson
Service was damage from fire. installed new grounding system. Phone #: ###-#### Inspection requested via web by Alan Lusk
Approved on temporary basis until such time is provided to complete a service change. Damaged unit not energized.
p/s o/h rec ok