Final | 7/2/2019 | 7/3/2019 | 7/3/2019 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Mike McCarrel Final ok
|
Final | 2/27/2019 | 2/28/2019 | 2/28/2019 | A | PART |
Rock A. Hudson
|
|
|
Final for wild dog/hyena building Phone #: ###-#### Inspection requested via web by Mike McCarrel Cody Riddle Head of plan review has approved the installation of an electric fence for the wild dog and hiena enclosures as an exeption to BCC 4-05-31(B). As per 210.8(B)(4)- Outdoor receptacle power supply for electric fence does require GFCI protection. To prevent nuisance tripping creating a dangerous situation for handlers unit would be ok to hardwire with a disconnecting means provided, 110.25 lockout acceptacle. General contractor to fill in hole in front of panels ASAP as per 240.24(A). Building D-5 TCO ok
|
Electrical Rough-In | 2/22/2019 | 2/22/2019 | 2/22/2019 | P | PASS |
Mark Moncarr
|
|
|
for sub-panels WD and WDG Phone #: ###-#### Inspection requested via web by Mike McCarrel Ok cover 2 sub panels on NE corner of hyena enclosure. Grds and newt seperated,
|
Electrical Rough-In | 2/13/2019 | 2/13/2019 | 2/13/2019 | P | PASS |
Rock A. Hudson
|
|
|
Underground for wild dog and hyena heated rocks Phone #: ###-#### Inspection requested via web by Mike McCarrel Areas noted underground rough in ok cover
|
Electrical Rough-In | 10/26/2018 | 10/29/2018 | 10/29/2018 | A | PASS |
Rock A. Hudson
|
|
|
Inspect ceilings for cover. Phone #: ###-#### Inspection requested via web by Jeremy Cloud Ceiling rough in ok cover
|
Electrical Rough-In | 8/21/2018 | 8/22/2018 | 8/22/2018 | A | PASS |
Rock A. Hudson
|
|
|
Please call Mike Phone #: ###-#### Inspection requested via web by Kevin Perez Discussed pools for animal use only shall comply with NEC 682, and direct burial depth for paved areas inside zoo shall not be concidered used for vehicular traffic since designed for pedestrian paths. 18" minimum depth required. Box installation in cinder block rough in ok cover
|
Electrical Rough-In | 5/29/2018 | 5/30/2018 | 5/30/2018 | A | PASS |
Rock A. Hudson
|
|
|
ufer ug // go to CM construction gate // Mike Phone #: ###-#### Rough in ok cover
|