Final | 10/23/2018 | 10/24/2018 | 10/24/2018 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jerry Moore corrections made final ok
|
Final | 10/22/2018 | 10/23/2018 | 10/23/2018 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jerry Moore 210.8 All outdoor receps shall be GFCI protected(Front door, Geustroom door, Master mechanical room door) 410.16 Luminares with open bulbs shall not be allowed.(Master closet chand.) 314.20. Boxes set back more than 1/4in shall have extender.(WP's in siding) 314.23. Boxes shall be ridgidly secured.(Garage man door WP) Laundry receps dead, Laundry fan dead, Powder bath recep Dead, WP left of master bed slider dead,Chand in dining room storage dead
|
Electrical Rough-In | 8/21/2018 | 8/21/2018 | 8/21/2018 | P | PASS |
James Ady
|
|
|
Floor heat inspection Phone #: ###-#### Inspection requested via web by Jerry Moore master floor heat only ok to cover
|
Electrical Rough-In | 5/30/2018 | 5/30/2018 | 5/30/2018 | P | PASS |
James Ady
|
|
|
Lloyd Phone #: ###-#### Rough in only no service. ok to cover
|