Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE18-02126
StatusFinaled
Name ENTERPRISE ELECTRIC
Site Address 420 S 5TH ST
Project Name 
Customer Number 
ePlanReviewNo
Description
New: electrical work for new parking lot
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/11/20187/12/20187/12/2018APASS
DetailsRock A. Hudson
We are requesting another final on this project. the corrections have been made. Thank you! Our contact is Larry ###-#### Phone #: ###-#### Inspection requested via web by Larry Looney Final ok
Final7/11/20187/11/20187/11/2018PFAIL
DetailsRock A. Hudson
Idaho Power is scheduled to connect power to the pedestal today.
we are requesting a final inspection for this project. Our contact is Larry,
###-####. Thank you! Phone #: ###-#### Inspection requested via web by Larry Looney
408.4- Circuit directory shall be complete and accurate. 1 20 amp breaker buried behind knock out and feeds photo cell.
Permanent Service6/13/20186/13/20186/13/2018PPASS
DetailsRock A. Hudson
We are requesting a Permanent Service inspection for this project.
Our contact is Larry, ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Larry Looney p/s u/g n ok
Final6/12/20186/13/20186/13/2018AFAIL
DetailsRock A. Hudson
We are requesting a final inspection for this project. Our contact is Larry
###-#### Phone #: ###-#### Inspection requested via web by Larry Looney
250.8(A)(6)- Thread forming machine screws that engage not less than 2 threads in the enclosure shall be used.
Permanent service inspection must be approved prior to final inspection. At final shall be labelled and circuit free of shorts.
Electrical Rough-In6/7/20186/8/20186/8/2018PPASS
DetailsRock A. Hudson
We are requesting an underground rough-in inspection for this project. Our contact is Larry, ###-#### Phone #: ###-#### Inspection requested via web by Larry Looney
Underground and pole bases rough in ok cover
Conference6/7/20186/7/20186/7/2018PDONE
DetailsRock A. Hudson
Larry requested a consult to clarify location of power pedestal. Phone #: ###-#### Inspection requested via web by Clint Tate
Discussed any requirements for pedistal for parking lot. Minimum work clearances and grounding cover by NEC. No additional ballards needed.