Final | 6/26/2018 | 6/27/2018 | 6/27/2018 | A | PASS |
Mark Moncarr
|
|
|
Bill Canfield is the contact Phone #: ###-#### Inspection requested via web by Tyler Ridley Ok final. #4 cu and 60a 3 pole brkr.
|
Final | 6/22/2018 | 6/25/2018 | 6/25/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Contact name is Bill Canfield Phone #: ###-#### Inspection requested via web by Tyler Ridley 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 7.5 m (25 ft) of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means.
|