Final | 9/13/2018 | 9/13/2018 | 9/13/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
|
Final | 9/12/2018 | 9/12/2018 | 9/12/2018 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk 110.3- Items shall be connected as per manufacturers instructions. Level 3 bath GFI has reverse polarity, Level 1 understair light not working. 210.8- Washer receptacle is located with in 6' of a sink and shall be GFCI protected. 210.12- Level 1 room has closet with clothes rod installed so shall have AFCI protected. 314.20- Where boxes installed in a wall with non combustible materials they shall not be set back more than 1/4" from surface with out box extensions installed. Kitchen counter receptacles. 348.30- FMC shall be secured with in 12" of each box. Disposal
|
Rough-In Permanent Service | 7/12/2018 | 7/12/2018 | 7/12/2018 | P | PASS |
James Ady
|
|
|
garage code 1001e Phone #: ###-#### Inspection requested via web by Alan Lusk rough in ok p/s u/g n ok
|
Electrical Rough-In | 7/11/2018 | 7/12/2018 | 7/12/2018 | A | CANC |
James Ady
|
|
|
garage code 1001e Phone #: ###-#### Inspection requested via web by Alan Lusk
|
Final | 7/12/2018 | 7/12/2018 | 7/12/2018 | P | CANC |
James Ady
|
|
|
garage code 1001e Phone #: ###-#### Inspection requested via web by Alan Lusk
|