Final | 9/27/2019 | 9/27/2019 | 9/27/2019 | P | PASS |
Tom Saunders
|
|
|
cesar Phone #: ###-####...corrections made...ok to final
|
Final | 9/25/2019 | 9/25/2019 | 9/25/2019 | P | FAIL |
Mark Moncarr
|
|
|
Cesar Phone #: ###-#### 1. 2 outside recepts need WR. 2. Spark rings needed in kitchen. 3. Horiz outlet under window needs changed to box to allow box fill. Blue shallow carlon used with holes drilled in back of box so excess wire could be pushed through. Also open ground at this location. Grounds were not inside box, they were pushed in wall.
|
Conference | 7/11/2018 | 7/18/2018 | 7/18/2018 | A | PASS |
Tom Saunders
|
|
|
Cesar Phone #: ###-####...wiring complete at time of inspection...rough in scheduled and resulted
|
Electrical Rough-In | 7/18/2018 | 7/18/2018 | 7/18/2018 | A | PASS |
Tom Saunders
|
|
|
Cesar Phone #: ###-####...walls and ceiling ok to cover...second rough inspection needs scheduled once feeds to house are installed and grounding for house panel
|