Permit Information
Permit NumberELE18-02662
StatusFinaled
Name ALLOWAY ELECTRIC CO INC
Site Address 101 S CAPITOL BLVD Unit: 930
Project Name 
Customer Number76721
ePlanReviewNo
Description
New: 1) Provide and install (1ea) 3-pole 100-amp circuit breaker to feed the new panel.
2) Provide and install (1ea) 100-amp MLO 120/240v panel with associated breakers.
3) Provide and install (1ea) lighting control panel.
4) Provide and install lighting
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final9/17/20189/18/20189/18/2018APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by steve ragan Final ok
Final9/17/20189/17/20189/17/2018PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by steve ragan
110.3- 4 receptacle outlets not working. 2 reception area, 1 knee space reception, 1 office old and crumbling. All not h
Final9/14/20189/17/20189/17/2018ACANC
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by steve ragan
Duplicate request.
Electrical Rough-In9/4/20189/4/20189/4/2018PPASS
DetailsRock A. Hudson
Rough-in Ceiling Phone #: ###-#### Inspection requested via web by steve Grid rough in ok cover
Electrical Rough-In8/30/20188/31/20188/31/2018PFAIL
DetailsRock A. Hudson
Ceiling Phone #: ###-#### Inspection requested via web by steve ragan
300.15- All cables shall terminate in a box. 12-2 mc stubbed out of wall in a office.
314 25- Several box covers missing through out. KO seals needed.
Electrical Rough-In7/19/20187/20/20187/20/2018PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by steve ragan
Discussed conference rm 7 receptacles minimum and 2 floor receptacles required,
Wall rough in ok cover