Final | 9/27/2018 | 9/27/2018 | 9/27/2018 | P | PASS |
Mark Moncarr
|
|
|
Key is in front outlet Phone #: ###-#### Inspection requested via web by Kevin Heideman Ok final.
|
Final | 9/17/2018 | 9/18/2018 | 9/18/2018 | A | FAIL |
Eric Story
|
|
|
Key is in front door outlet Phone #: ###-#### Inspection requested via web by Kevin 210.52 Shall have a receptacacle l;ocated and endd of penisula
|
Conference | 7/19/2018 | 7/19/2018 | 7/19/2018 | P | PASS |
Tom Saunders
|
|
|
please call 30 min before arrival Phone #: ###-#### Inspection requested via web by Kevin Heideman...question on grounding of service since no uffer could be found or installed to attach to...oked 2 ground rods being installed 6' apart
|
Rough-In Permanent Service | 7/19/2018 | 7/19/2018 | 7/19/2018 | P | PASS |
Tom Saunders
|
|
|
please call 30 min before arrival Phone #: ###-#### Inspection requested via web by Kevin Heideman...rough ok to cover...p/s u/g new ok
|