Final | 8/8/2018 | 8/9/2018 | 8/9/2018 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Kelly Tarter Job complete, Final ok
|
Permanent Service | 7/30/2018 | 7/30/2018 | 7/30/2018 | P | PASS |
Rock A. Hudson
|
|
|
Available fault current update, 46K previously stated was at transformer. 65k rated gear being installed. p/s u/g rec ok
|
Permanent Service | 7/23/2018 | 7/23/2018 | 7/23/2018 | P | FAIL |
Rock A. Hudson
|
|
|
110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage at least equal to the current that is available at the line terminals of the equipment. Contractor to verify AFC
|