Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberELE18-02894
StatusFinaled
Name MOUNTAIN HOME ELECTRIC
Site Address 3701 W CRESCENT RIM DR Unit: 107
Project Name 
Customer Number 
ePlanReviewNo
Description
Alteration or Repair: remodel kitchen, add LED lighting
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/24/20191/25/20191/25/2019APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Robert Carter
Corrections made. Final ok
Final1/15/20191/16/20191/16/2019PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Robert Carter
210.12- All outlets located in bedroom areas shall have GFCI protection.
314.25- All boxes shall have covers. HVAC control switch in hallway.
Electrical Rough-In8/13/20188/14/20188/14/2018APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Robert Carter
Light boxes to be cut in to ceiling, Ceiling boxes mounted at rough in shall have 1"+ mud rings. Rough in ok cover
Conference7/31/20187/31/20187/31/2018PDONE
DetailsRock A. Hudson
confirmation on application Phone #: ###-#### Inspection requested via web by Robert Carter
Discussed type of lighting used for plenum above a 1 hr fire rated ceiling. All penetrations shall have at least a 1 hr fire rated box installed and all wiring installed in plenum area shall be plenum rated. Halo recess cans do ot have a fire rating. Contactor looking at a small LED surface mount luminaire that mounts to 2 hr rated remodel electrical box.