Final | 10/2/2018 | 10/2/2018 | 10/2/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Robert Carter Final ok
|
Final | 9/20/2018 | 9/21/2018 | 9/21/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Please use side gate for entry if no one is home Phone #: ###-#### Inspection requested via web by Robert Carter 210.8(A)(2)- All receptacles located in hobby room shall have GFCI protection. Refer/ freezer. 406.9(A)- All receptacles installed outdoors in damp or wet locations shall be weather resistant type. 406.12- All receptacles installed in addition to residential garage shall be tamper resistant type.
|
Electrical Rough-In | 8/23/2018 | 8/24/2018 | 8/24/2018 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Robert Carter...ok to cover
|