Final | 11/14/2018 | 11/15/2018 | 11/15/2018 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI... corrections made ok to final
|
Final | 11/13/2018 | 11/14/2018 | 11/14/2018 | A | FAIL |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI NEC 250.52 Ground rod shall not be less than 8ft. in lenght. Supplemental Electrode thas be cut off.
|
Final | 11/5/2018 | 11/5/2018 | 11/5/2018 | P | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI... 1..hood needs breaker lock out installed-hard wired appliance 2..sub panel needs labelled correctly and legible 3..ground rods shall be minimum 6ft apart stated at time of service inspection and not addressed 4..riser at service shall be strapped withinb3ft
|
Rough-In Permanent Service | 8/20/2018 | 8/21/2018 | 8/21/2018 | A | PASS |
Rock A. Hudson
|
|
|
Walk around left of house to back yard to access new service and addition. Phone #: ###-#### Inspection requested via web by TOM BICANDI Garage wiring not ready, sub-panel to be connected after old service location disconnected. Ground rods shall have 6' minimum distance between rods as per 250.53. Family room and bedroom rough in ok cover p/s o/h rec ok
|