Final | 10/5/2018 | 10/5/2018 | 10/5/2018 | P | PASS |
Rock A. Hudson
|
|
|
1 hr notice for access coordination Phone #: ###-#### Inspection requested via web by Lee VanSchoiack No card posted Final ok
|
Electrical Rough-In | 9/28/2018 | 9/28/2018 | 9/28/2018 | P | PASS |
Rock A. Hudson
|
|
|
grid ceiling, Call 1hr before to coordinate access Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Grid for areas previously noted rough in ok cover
|
Electrical Rough-In | 8/28/2018 | 8/29/2018 | 8/29/2018 | P | PASS |
Rock A. Hudson
|
|
|
call Lee ###-#### 30 minutes prior for access info Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Floor receptacle required by 210.71 was not included on print. Conference room 360 sq. ft. minimum of 2 floor receptacles required, minimum number of receptacles required for room will be satisfied if 2 floor receptacles are installed. Offices, conference room, exersize rooms Wall rough in ok cover
|