Final | 5/14/2019 | 5/14/2019 | 5/14/2019 | A | PASS |
Daryl DeGrange
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks final ok
|
Electrical Rough-In | 11/28/2018 | 11/28/2018 | 11/28/2018 | P | PASS |
James Ady
|
|
|
Open walls in house inspection Phone #: ###-#### Inspection requested via web by Jason Wicks Pantry, Entry, Den and front bed Pocket door ok to cover
|
Rough-In Permanent Service | 11/12/2018 | 11/13/2018 | 11/13/2018 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks New service location p/s o/h rec ok
|
Electrical Rough-In | 8/31/2018 | 8/31/2018 | 8/31/2018 | A | PASS |
Rock A. Hudson
|
|
|
House is wired for outside lights. Wire is on soffit. When owner decides what light we will use cut in box for exact location. Phone #: ###-#### Inspection requested via web by Jason Wicks Service change is planned. Loose wires to terminate in new panel. Rough in ok cover
|
Electrical Rough-In | 8/29/2018 | 8/30/2018 | 8/30/2018 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks 300.15- All wiring shall terminate in a box.Loose wiring in attic where addition meets existing house. 334.30-NM cable shall be secured with in 12" of playhouse panel. 590.6- All receptacles installed for construction shall have GFCI protection. 220.1- Provide service calculation for house when additions complete.
|