Final | 4/4/2019 | 4/4/2019 | 4/4/2019 | P | PASS |
Rock A. Hudson
|
|
|
Fiinal ok
|
Final | 3/5/2019 | 3/6/2019 | 3/6/2019 | A | NR |
Rock A. Hudson
|
|
|
Please call ahead 30 minutes prior to arrival. Ron is our site contact at ###-#### Phone #: ###-#### Inspection requested via web by Kerri Hamilton All items and areas checked ok. BLD still under review. Unable to document until issued.
|
Final | 2/28/2019 | 3/1/2019 | 3/1/2019 | A | PART |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Over stair from level 3 to 4 not complete, and refrigerator on level 2 not on wheels. Asked to move GFCI to readily accessible location and will check when inspect stair lighting. Signed Temp occupancy. TCO ok
|
Final | 2/27/2019 | 2/28/2019 | 2/28/2019 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 210.8(B)- All receptacle outlets located with in 6' of a sink shall have GFCI protection. Janitors closet basement only, refers, ice makers on all floors. Level 5 drinking fountain GFCI, Level 5 patio GFI in-op, Inspect level 5 board room grid. Over stair between level 4 and 5 not complete.
|
Electrical Rough-In | 2/22/2019 | 2/25/2019 | 2/25/2019 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Level 2 elevator lobby grid and level 2 conference room grid rough in ok cover
|
Electrical Rough-In | 2/18/2019 | 2/19/2019 | 2/19/2019 | A | PART |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Level 2 grid except 227 conferene room rough in ok cover
|
Electrical Rough-In | 2/18/2019 | 2/19/2019 | 2/18/2019 | P | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
|
Electrical Rough-In | 1/22/2019 | 1/23/2019 | 1/23/2019 | A | PASS |
Rock A. Hudson
|
|
|
As early as possible. Phone #: ###-#### Inspection requested via web by Kerri Hamilton Level 5 grid except board room rough in ok cover
|
Electrical Rough-In | 1/22/2019 | 1/22/2019 | 1/22/2019 | P | CANC |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
|
Electrical Rough-In | 1/9/2019 | 1/10/2019 | 1/10/2019 | A | PART |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 590.6(A)(2)- Trim out temp power part of building power GFCI protection shall be provided during construction. Few plug in GFCI being used, most are not using. Level 4 grid rough in ok cover. OK for furniture.
|
Final | 1/4/2019 | 1/4/2019 | 1/4/2019 | P | PART |
Rock A. Hudson
|
|
|
Partial Final - 3rd Floor Temp Occ Phone #: ###-#### Inspection requested via web by Kerri Hamilton Level 3 for furniture only OK
|
Electrical Rough-In | 1/4/2019 | 1/4/2019 | 1/4/2019 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Level 3 cloud grid rough in ok cover
|
Electrical Rough-In | 1/2/2019 | 1/2/2019 | 1/2/2019 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Level 3 office grid only cloud not ready rough in ok cover
|
Electrical Rough-In | 12/7/2018 | 12/7/2018 | 12/7/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Kount lobby hard lid in entrance, storage room walls, basement locker rooms hard lids rough in ok cover
|
Electrical Rough-In | 11/30/2018 | 11/30/2018 | 11/30/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Basement storage and locker room wall rough in ok cover
|
Electrical Rough-In | 10/23/2018 | 10/24/2018 | 10/24/2018 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Level 5 hardlids rough in ok cover
|
Electrical Rough-In | 10/4/2018 | 10/5/2018 | 10/5/2018 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Level 2 interior wall rough in ok cover
|
Electrical Rough-In | 10/3/2018 | 10/4/2018 | 10/4/2018 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Level 3 kitchen wall and level 5 panel wall rough in ok cover
|
Electrical Rough-In | 10/1/2018 | 10/1/2018 | 10/1/2018 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton North and west and interior except panel wall rough in ok cover
|
Electrical Rough-In | 9/27/2018 | 9/28/2018 | 9/28/2018 | A | PART |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton BCC BCC Section 4-05-23 UNLAWFUL TO CONCEAL It shall be unlawful for any person, to cover up or in any way conceal any electrical wiring, cables, conduits or other equipment until the same has been inspected and approved by an Electrical Inspector. (6338, Added, 08/03/2004) Remove insulation in north and west walls South and east and bay window exterior walls only ok cover
|
Electrical Rough-In | 9/21/2018 | 9/21/2018 | 9/21/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Level 4 interior walls rough in ok cover
|
Electrical Rough-In | 9/20/2018 | 9/21/2018 | 9/21/2018 | P | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
|
Electrical Rough-In | 9/13/2018 | 9/13/2018 | 9/13/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Level 3 interior wall rough in ok cover
|
Electrical Rough-In | 9/11/2018 | 9/11/2018 | 9/11/2018 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 2nd floor exterior walls only ok to cover
|
Electrical Rough-In | 9/5/2018 | 9/5/2018 | 9/5/2018 | A | PASS |
James Ady
|
|
|
4th floor Phone #: ###-#### Inspection requested via web by Kerri Hamilton 4th floor Exterior walls only ok to cover
|
Electrical Rough-In | 8/31/2018 | 8/31/2018 | 8/31/2018 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Level 3 perimeter walls only rough in ok cover
|