Final | 10/11/2018 | 10/15/2018 | 10/15/2018 | P | PASS |
James Ady
|
|
|
lock box code 8953 or 5389 Phone #: ###-#### Inspection requested via web by Darryn Coburn Corrections made final ok
|
Final | 10/10/2018 | 10/11/2018 | 10/11/2018 | A | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn... 1..hot/neutral reverse on outlet..middle hair station 2..outlets (x 2) within 6ft of sink shall have GFI protection-pedicure rm 3..junction box or outlet box incomplete-facial rm 4..outlet within 6ft of sink shall have GFI protection-storage/dryer area sink
|
Electrical Rough-In | 9/5/2018 | 9/6/2018 | 9/6/2018 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn...wall cover only...new wall at entry, all other wall work fished in...ceiling work needs done and inspected-fixture whips laying on grid
|