Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberELE18-03442
StatusFinaled
Name GLENN ELECTRIC
Site Address 6177 E HOOTOWL DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: ROUGH & PERM SERVICE
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final1/15/20191/16/20191/16/2019APASS
DetailsRock A. Hudson
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn
Final ok
Permanent Service11/1/201811/1/201811/1/2018PPASS
DetailsJames Ady
Permanent service p/s u/g n ok
Rough-In Permanent Service9/20/20189/21/20189/21/2018PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Bob Glenn corrections made rough in ok
Rough-In Permanent Service9/19/20189/20/20189/20/2018AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Bob Glenn
Attic upstairs boxes trimmed at rough in, christmas switches located in entry closet, 327 has pics of 12-2 stubs in family room off kitchen.
250.24- Grounding electrode conductor connection shall connect to grounded conductor in 1 location only. Jumper installed from main breaker panel to meter base creating parallel path between grounded conductor and grounding conductor.
250.68(A)- Connection to concrete encased electrode shall remain accessible. Need mudring.
300.4- Where NM cable is run through bored holes that do not maintain 1 1/4" from framing surface they shall be protected by nail plates. By garage man door, above mudroom switches, pantry wire to under stair light.
348.26- Maximum number of bends in FMC to single garage attic shall not exceed 360 degrees.