Final | 11/30/2018 | 11/30/2018 | 11/30/2018 | P | PASS |
James Ady
|
|
|
Call for access code, thank you Phone #: ###-#### Inspection requested via web by kim grundhauser final ok
|
Permanent Service | 9/18/2018 | 9/18/2018 | 9/18/2018 | A | PASS |
James Ady
|
|
|
call with any questions thank you Phone #: ###-#### Inspection requested via web by kim grundhauser Corrections to service made. p/s u/g n ok
|
Rough-In Permanent Service | 9/13/2018 | 9/14/2018 | 9/14/2018 | A | FAIL |
Rock A. Hudson
|
|
|
call with any questions thank you Phone #: ###-#### Inspection requested via web by kim grundhauser 300.15- Connections shall be contained in a box. temp receptacle locations wiring stripped and hanging out of boxes. 314.25- Recessed junction box covers shall be completely installed as per instructions. Family room. 408.3(A)(2)- Barriers shall be installed ar service entrance line side terminals. House OK to insulate, reinspect service.
|