Permit Information
Permit NumberELE18-03519
StatusFinaled
Name B & J ELECTRIC INC
Site Address 11522 W FAIRVIEW AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
New: New 400 amp overhead service, distribution panels, transformer, lighting and general purpose receptacles.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/21/201811/26/201811/26/2018APASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Heath Thomas...ok to final
Permanent Service10/2/201810/3/201810/3/2018APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Heath Thomas
9755 amps posted available fault current with max of 35k @ 480v. p/s o/h n ok
Permanent Service10/2/201810/3/201810/2/2018PCANC
DetailsTom Saunders
Phone #: ###-#### >> Inspection requested via web by Heath Thomas Inspection cancelled from web by: Heath Thomas
Permanent Service10/1/201810/2/201810/1/2018ACANC
DetailsTom Saunders
Phone #: ###-#### >> Inspection requested via web by Heath Thomas Inspection cancelled from web by: Heath Thomas
Permanent Service9/24/20189/25/20189/25/2018AFAIL
DetailsEric Story
Please call Corey @ ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Heath Thomas
AFC calc required prior to service being energized
Conference9/13/20189/14/20189/14/2018ADONE
DetailsEric Story
Conference for service grounding requirements. Corey ###-#### is point of contact and will be on site from 9-2 Friday. Phone #: ###-#### Inspection requested via web by Heath Thomas
Discussed grounding of building steel and riser,no uffer was pure so 2 ground rods is sufficient to ground plate and all others to it.