Final | 11/21/2018 | 11/26/2018 | 11/26/2018 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas...ok to final
|
Permanent Service | 10/2/2018 | 10/3/2018 | 10/3/2018 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas 9755 amps posted available fault current with max of 35k @ 480v. p/s o/h n ok
|
Permanent Service | 10/2/2018 | 10/3/2018 | 10/2/2018 | P | CANC |
Tom Saunders
|
|
|
Phone #: ###-#### >> Inspection requested via web by Heath Thomas Inspection cancelled from web by: Heath Thomas
|
Permanent Service | 10/1/2018 | 10/2/2018 | 10/1/2018 | A | CANC |
Tom Saunders
|
|
|
Phone #: ###-#### >> Inspection requested via web by Heath Thomas Inspection cancelled from web by: Heath Thomas
|
Permanent Service | 9/24/2018 | 9/25/2018 | 9/25/2018 | A | FAIL |
Eric Story
|
|
|
Please call Corey @ ###-#### with any questions. Phone #: ###-#### Inspection requested via web by Heath Thomas AFC calc required prior to service being energized
|
Conference | 9/13/2018 | 9/14/2018 | 9/14/2018 | A | DONE |
Eric Story
|
|
|
Conference for service grounding requirements. Corey ###-#### is point of contact and will be on site from 9-2 Friday. Phone #: ###-#### Inspection requested via web by Heath Thomas Discussed grounding of building steel and riser,no uffer was pure so 2 ground rods is sufficient to ground plate and all others to it.
|