Permit Information
Permit NumberELE18-03533
StatusFinaled
Name BEACON ELECTRIC
Site Address 111 N MAIN ST Unit: 200
Project NameDr. Boerner, MD - Suite #200
Customer Number 
ePlanReviewNo
Description
moving switches and outlets in lobby and new room
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/14/201810/15/201810/15/2018APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Ron Zimmerman Final ok
Final10/11/201810/12/201810/12/2018AFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Ron Zimmerman
210.8(B)- Receptacles located within 6' of a sink shall have GFCI protection. Exam room
Electrical Rough-In9/17/20189/17/20189/17/2018APART
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Ron Zimmerman
Walls covered with drywall prior to inspection, Confirmed medical grade MC used in exam room and EMT used on existing receptacle location however an equipment ground needs added to existing EMT runs to be complient. No issues with reception area only exam room. Will not require removal of drywall due to minimal work performed. Will check existing receptacles on final.
Electrical Rough-In9/14/20189/14/20189/14/2018PFAIL
DetailsRock A. Hudson
Ron Phone #: ###-####
517.13- Wiring methods in patient care space shall have a effective ground fault current path to all receptacle and switch locations with in patient care space. Confirm all receptacles and the switch in exam room E contain proper wiring method. Did not leave correction on site had verbal with Ron.