Final | 8/7/2019 | 8/7/2019 | 8/7/2019 | P | PASS |
Tom Saunders
|
|
|
Leon Phone #: 208###-####...corrections made
|
Final | 8/5/2019 | 8/5/2019 | 8/5/2019 | P | FAIL |
Tom Saunders
|
|
|
Leon Phone #: ###-####... corrections not complete GC of job is aware need corrections left to address outlets in panelling, light dwn strs hall closet 314.20, 410.16
|
Final | 8/2/2019 | 8/2/2019 | 8/2/2019 | P | FAIL |
Tom Saunders
|
|
|
Leon Phone #: ###-####...
to much to list...see posted correction notice
REINSPECTION FEE APPLIED
|
Electrical Rough-In | 8/1/2019 | 8/1/2019 | 8/1/2019 | P | PASS |
Tom Saunders
|
|
|
Leon- underground cover inspction Phone #: ###-####... pipe feeding pool panel was not inspected at time of installation and neither GC or Electrical contractor will admit to work depth and length of pipe feeding pool verified be string...190ft unable to verify how pipe was run to pool panel to get true depth...over 70% of pipe is under driveway GC and electrical contractor taking full responsibility for circuit wiring to pool
|
Final | 7/30/2019 | 7/30/2019 | 7/30/2019 | P | FAIL |
Tom Saunders
|
|
|
Leon Phone #: ###-####... too many corrections pool power needs addressed no GFCI protection
|
Rough-In Permanent Service | 11/6/2018 | 11/6/2018 | 11/6/2018 | P | PASS |
Mark Moncarr
|
|
|
requesting a cover inspection to proceed also an okay to energize meter please advise have a great Tuesday thankyou for your time Phone #: ###-#### Inspection requested via web by leon ramirez Ok cover. 3 outlets needed, 1 on each wall in foyer(entry) Each wall is 3ft or more in length. 2- D/W's in kitchen need to be hard wired, or outlets moved under sink for them to be readily accessible. Not going to require outlet within 12ft of adjacent outlet on framed in bed upper level as it would be a trip hazard. p/s u/g n ok
|