Description
upgrade panel on detached garage to 200 amp service
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final3/15/20193/18/20193/18/2019APASS
DetailsMark Moncarr
James Phone #: ###-#### Ok final. Bushings used, grounding identified, grds and neut seperated in shop panel.
Permanent Service3/11/20193/12/20193/12/2019APASS
DetailsMark Moncarr
James Phone #: ###-#### p/s o/h n ok
Permanent Service3/7/20193/8/20193/8/2019AFAIL
DetailsMark Moncarr
James Phone #: ###-#### 200a feed through meter main used. Need 100a 2-pole brkr placed below 200a main. Wires terminated on feed through lugs are sized for a 100a panel. Also need equipt ground wire, and attach grounding electrode conductor to 2nd ground rod.
Electrical Rough-In1/14/20191/14/20191/14/2019PNR
DetailsMark Moncarr
James-forgot to call in the conference call-still needs R.I.-please call to meet and for direction Phone #: ###-####